Electrical DB pictures
I have uploaded below a few pictures of electrical DB being installed at a high-rise office-building project. I only have enough time for these few pictures today, but I will be sending a more detailed post on the DB installation soon. Plus a few more of the DB pictures maybe.In the meantime, if you have the time, check out the following link. It is a link on how to convert your car into an
Electrical DB installation
The electrical DB (distribution boards) for high-rise office installations shall be non-ventilated, naturally cooled, metal enclosed type, flush fronted and suitable for front access and shall be built to comply with IEC 60439-1. All louvers shall be covered with wire mesh.The distribution boards shall contain MCCB (moulded case circuit breakers), MCB (miniature circuit breakers), RCD (residual
Labels:
DB
,
Distribution boards
,
Electrical DB
Electrical busbars
The electrical busbars inside the switchboards shall be of plain hard-drawn, high conductivity, electrolytic copper bars in accordance with BS EN 13601: 2002, and of adequate rectangular cross-section to carry continuously the specified current without overheating and shall be rigidly mounted on non-hygroscopic insulators so as to withstand any mechanical forces to which they may be subjected
Electrical DB wiring
Following is a sample specifications for the wiring of an electrical DB. Refer the section on Electrical DB installation for specification details on the construction of distribution boards.
Photo 1 - Internal wiring of an electrical DB
Terminals for external conductors All conductor terminals shall be suitable for copper conductors.
All cable termination assemblies shall have facilities for
Photo 1 - Internal wiring of an electrical DB
Terminals for external conductors All conductor terminals shall be suitable for copper conductors.
All cable termination assemblies shall have facilities for
Labels:
Building electrical
,
DB
,
Distribution boards
,
Electrical DB
Switchboard electrical earthing
Following is a picture showing the earthing busbar of a main switchboard. Below the picture is a simple performance specifications for the grounding of the switchboard.
The are also two more posts on switchboard installation check and switchboard electrical tests. The latter is a general list of tests and inspections that are usually required of a major switchboard such as main switchboards and
The are also two more posts on switchboard installation check and switchboard electrical tests. The latter is a general list of tests and inspections that are usually required of a major switchboard such as main switchboards and
Electrical switchboard installation
The following is a sample perfomance specifications for the assembly and installation of switchboards in an electrical contract for a new multi-storey office building.ScopeThe scope of this section is to set down briefly the requirements, methods, materials, workmanship, standards and regulations in connection with the complete assembly of switches, starters, and/ or control devices as used in an